🔧 Technical Specifications
- Input Types: Supports multi-input configurations, including thermocouples, RTDs (3-wire), DC voltage, and DC current inputs.
- Control Outputs:
- OUT1: Options include relay contact (3 A at 250 V AC), non-contact voltage (12 V DC ±15%, max 40 mA), or direct current (4–20 mA DC, max load resistance 600 Ω).
- OUT2: Available when heating/cooling control options (DR, DS, DA) are selected, with similar output configurations as OUT1.
- Event Outputs: Up to 4 event outputs (EV1–EV4), each with relay contact output (3 A at 250 V AC resistive load).
- Event Inputs: Supports up to 4 digital inputs for external control, enabling pattern selection and other functions.
- Display: Features an 11-segment LCD display with three-color PV indication (green, orange, red) for easy status monitoring.
- Program Capacity: Capable of storing up to 16 patterns with 16 steps each, totaling 256 programmable steps.
- Power Supply: Operates on 100–240 V AC or 24 V AC/DC, depending on the model.
- Accuracy: ±0.2% of the measuring range for thermocouple inputs; ±0.1% for RTD inputs.
- Protection Rating: Front panel conforms to IP66 standards, offering resistance to dust and water ingress.
- Dimensions: 96 x 96 x 98.5 mm (W x H x D).
🛠️ Additional Features
- Serial Communication: Supports Modbus ASCII/RTU and Shinko protocols for integration with various systems.
- Monitoring Software: Compatible with SWC-PCA101M and SWM-PCA101M software for data monitoring, editing, and uploading. Notably, when using a USB communication cable, the PCA1 does not require separate power for configuration.
- Cooling Methods: Offers selectable cooling methods (air, oil, water) for OUT2 when heating/cooling control options are utilized.
For detailed information on installation, configuration, and operation, you can refer to the official instruction manual available here: Shinko PCA1 Instruction Manual.
If you need assistance with specific configurations or have further questions about the PCA1 Series, feel free to ask.